    What can cause an error code EPHO on the ATV21 and ATV212 (also S-Flex) drives?

    Issue:
    ATV212: EPHO or output phase loss fault

    Product Line:
    ATV212, ATV21, S-Flex

    Environment:
    All models and serial numbers

    Cause:
    Motor may not be connected.

    Resolution:
    Check that the motor is connected to the drive. 
    If the unit has a bypass option you will have to disable the output phase loss protection by setting F605 to 0.