    How is the ATV312 default display changed to show a different monitored parameter?

    Issue:
    How is the ATV312 default display changed to show a different monitored parameter?

    Product Line:
    ATV312  ATV31

    Environment:
    All

    Cause:
    Preference is to normally display a parameter such as motor current or motor torque, not the factory default of output frequency.

    Resolution:
    Go to SUP menu and display the parameter to be used as a default display ( e.g. LCr or Otr ).  Press ENT once to show the current value of that parameter.  Then press and hold ENT for about 2 seconds and the display will flash, indicating the process is complete.