    XW6048 W96 Cannot Equalize.

    Issue:
    W96 cannot equalize

    Product Line:
    Conext XW/XW+ , Conext SW

    Environment:
    On-grid or off-grid with batteries in need of equalization.

    Resolution:
    Change battery type if your batteries should be equalized. Gel or AGM batteries should not be equalized. 
    Check for presence of AC. Make sure Charge and Equalize are enabled. Verify the Xantrex XW AGS trigger is set to Stop Float. If Stop V is enabled, then the voltage level should be above the Eqlz Voltage level. 
    Make sure that the charging is not blocked by either the Charge Block setting or by Load Shave.  When Load Shave is Enabled, the charger is effectively disabled until the batteries get close to LBCO.

    Cause:
     No qualified AC power source, AC input is not qualified, or the charge setting is not adequate. 
    The selected battery type should not be equalized.