    What is the meaning of the B, C, D, K and Z curves for C60 Multi-9 circuit breakers?

    Issue:  
    What do the B curve, C curve, D curve, K curve and Z curve designations mean on Multi 9 breakers?

    Product Line:
    Circuit Breakers

    Environment:
    Applies to the ac rated C60 Multi-9 devices

    Resolution:
    For C60 Multi-9 devices, ac rated, the following is the meaning of the trip curves:
    B curve: 3.2 - 4.8 times amp rating for UL489 and UL1077 (3 - 5 times amp rating for IEC)
    C curve: 7 - 10 times amp rating
    D curve: 10 - 14 times amp rating
    K curve: 10 - 14 times amp rating
    Z curve: 2.4 to 3.6 times amp rating
    Trip curves are included in the 0860CT0201 catalog.