    What is the pin-out of the RJ45 socket of an ATV31 / 312 for connection of Modbus, CanOpen and PowerSuite cables

         The RJ45 socket of the ATV31/312 can be used for connection to the following networks and accessories:


         a PLC via a Modbus bus or via a CANopen network
         a PC/laptop loaded with PowerSuite software
         The VW3A31101 remote display terminal

         The Pin out of the RJ45 socket of the ATV31 is as follows:


         Pin no.                            ATV31 RJ45                         Comments          
         RJ45
     

            1                                       CAN high                           CAN-H - Signal for CANopen communication 
     
            2                                       CAN low                             CAN-L - Signal for CANopen communication 
     
            3                                       CAN GND                          CAN-GND - Signal for CANopen communication 
     
            4                                           D_B                               Signal for MODBUS communication 
     
            5                                           D_A                                Signal for MODBUS communication 
     
            6                                            NC                                 Not used 
     
            7                                          10 Volts                           0-10 V voltage supplied by the ATV31/312 which can be used to supply the 

            8                                           0 Volts                            converter when connected using PowerSuite software  

        Important clarification
     

       
       For Modbus communication, the signals used for the ATV31 /312 are D-B and D-A only -  the other connections are not used.

       For CANopen communication, the signals used for the ATV31 / 312 are CAN-H, CAN-L and CAN-GND -  the other connections are not used.

       With the VW3A31101/ VW3A1006/7remote display terminal, the signals used are D-B and D-A as well as the power supply.

      Caution: Lengths of cables need to be observed as too greater voltage drop in network connections may cause a malfunction.