    VAMP 321 arc flash sensors no longer functions after connecting a VAMP 10L module

    Issue
    After connecting a VAMP 10L module to the VAMP 321 relay the VAMP 321 arc flash sensors no longer triggers a trip.

    Product Line
    VAMP 321
    VAM10L

    Cause    
    This issue may be caused by connecting the VAMP 10L module to the VAMP 321 incorrectly.

    Resolution
    Verify that the communication port on the VAMP 321 matches that on the VAMP 10L. If they do not match correct this then reconfigure the connection under the ARC Protection screen within VAMPset and write these changes to the VAMP 321. Finally confirm functionality.