    How long does it take the digital input for logic discrimination (ZSI) to be recognized by the Sepam relay?

    Issue
    User wishes to know how long it takes the digital input for ZSI to be recognized by Sepam relay

    Product Line
    Sepam series 20
    Sepam series 40
    Sepam series 80

    Environment
    Performance

    Resolution
    It takes approximately 13 ms (one cycle time of the control reading) operating time for the relay to recognize and react to an input change.

    Note: For a Sepam series 20, only input I13 can be used to receive a blocking reception.