    The ATV71 has LI2 assigned for run reverse. Why does the drive continue to run forward when LI2 goes high?

    Issue:
    ATV71 has run reverse command assigned to LI2 but the drive continues to run forward when LI2 is activated, 2 wire control.

    Product Line:
    Altivar 61, Altivar 71.

    Environment:
    All models, All serial numbers.

    Cause:
    Drive is not responding to the command to run reverse.

    Resolution:
    In 2 wire control, logic input LI1 is assigned to run forward. LI1 must be removed when switching to run reverse.  If the drive receives a run reverse command without removing the run forward command, it will continue to run forward.  The same logic holds true when switching from reverse to forward.