in location

OR

I'm looking for

  • Wholesalers
    • Uncheck All Check All
  • EXPERTISE
    • Expand
    • Expand
    • Expand
    • Uncheck All Check All
  • Switchboard Manufacturers
    • Uncheck All Check All
OR

The best way to see what Clipsal electric products can do for your home is seeing them in action at a Clipsal Powerhouse Display Centre.

Product stock may vary according to location. If you're after a specific product range, please check with your chosen location before visiting.

10 Results
    Load More Load Complete
    Change Location

    Setting up a WRITE_Var command to have a M340 PLC write data over a Serial (Modbus) link.

    First in your Unity program open the configuration and double click on the serial port.


    Configure the serial port as needed for your application.
    Note: The port must be set to Master for the WRITE_Var to function.

    In this example the port is set for RS485, 19200,8,E,1
    The Rack, Module, Channel (r.m.c) for the Serial port is always 0.0.0 for a M340 processor




    Next go to Tools and Project Settings



    In the Project Settings that the last 3 items in the Data types field are checked off.
    This will allow us to directly enter Arrays into our project rather than having to first declare them as variables.



    Next add a ADDM block to your program, link the OUT pin to the ADR pin of the Read_Var block, and enter the appropriate String to the IN pin.
    For Modbus communication the syntax for the IN pin of the ADDM block uses the form r.m.c.e where:
    r = rack
    m = module
    c = channel
    e = equipment

    The equipment is the slave Modbus address.
    Remember that this input is a String so you need ' before and after the text.

    Next configure the remaining parameters of the WRITE_Var where:

    OBJ = String declaring the type of object to read (%MW or %M)
    NUM = The starting register address in the slave TCP/IP device of the object type
    NB = The # of registers to read
    RECP = Array of length NB where the data to be written is stored.
    GEST = Array of length 4 where the Management Exchange table for the WRITE_Var is located

    Note: The Array's are of type INT if declared as variables.


    This example will write 5 registers from %MW10-14 to %MW101-105 in a slave at Modbus address 15

     

    Didn’t find what you were looking for?

    Try Searching Again View Our Categories

    Need further assistance?

    Our Customer Care department provides total customer service solutions for our residential, industrial and commercial applications.

    Get Assistance