    What causes error 32600 in a SY/MAX controller?

    Error code 32600 is the Hardware Diagnostic Error.
    Possible causes:
    1) May be any module in CPU rack (usually LI or LTI)
    2) Module series incompatibility

    Recovery procedure:
    1) Check for series incompatibility. Determine if a Model 700 processor is used with pre-series C Analog or pre-series H Local Interface module in CPU rack. Both modules will not operate properly in CPU rack. Replace with later series modules.
    2) Switch power off. Check power supply according to Section 2 of Troubleshooting Guide.
    3) Replace LI, CPU or any modules in the rack where needed.

     