    Concept 2.6 - During Download Changes the PLC sporadically stops with Stop Code 0004 (Logic CheckSum Error)

    Goals and Symptoms

    Concept 2.6 - During Download Changes the PLC sporadically stops with Stop Code 0004 (Logic CheckSum Error)
    The problem might occur if the 140CPUx341x A EXEC rev 1.40 or 140CPU53414 B EXEC rev 1.12
    are used in the application and the PLC Memory Defragmentation is activated.
     

    Facts and Changes

    Reason: In some cases the Defragmentation changes administration data without changing
    the CheckSum.

    This problem does not occur with
    140CPUx341x A EXEC rev 1.39 and lower
    140CPU53414 B EXEC rev 1.11 and lower

    Causes and Fixes

    The problem will be fixed with
    140CPUx341x A EXEC rev 1.41
    140CPU53414 B EXEC rev 1.13