    What causes an 'OL9-1600 Not logged in to controller' error in Concept?

    This is typically a modbus timeout error.

    • Verify that the transmit and receive buffers are set to High in the PC's COM1: port parameters.
    • Try to connect to the PLC in ASCII mode at 2400 baud rate.
    • Is the laptop running off a low battery?
    • If the PLC is a Momentum, look for a bent pin.
    • Are Allen Bradley drivers enabled?
    • It may be necessary to jumper out the handshaking (DTR/DSR) in the cable. The modified pinouts are included in the attached files.

    Compact_momentum_RJ45 to DB9.zip DB9 To DB9 Pinout.zip

    Legacy KB System (APS) Data: RESL198297 V2.0, Originally authored by DaSo on 04/17/2009, Last Edited by DaSo on 02/27/2013
    Related ranges: Concept