    Procedure for adding an IP address onto a ProworX32 project for a Momentum 171CCC9x0 x0 M1E processor.

    Goals and Symptoms

    Procedure for adding an IP address onto a ProworX32 project for a Momentum 171CCC9x0 x0 M1E processor.

    Causes and Fixes


    · Start up ProworX32
    · Open your project


    · Select Configuration


    · Enter a value into the Config Extension Size (ex. 200)
    · This value can be modified later depending on the Config Extension Used value


    · Select Configuration Extensions
    · Check and highlight TCP/IP
    · Enter New IP and Subnet Mask info


    · Save project


    · Select Communications
    · Select which form of connection you currently have to download your project.(Modbus, Modbus Plus or TCP/IP)
    · Or enter the PRODUCTS current IP address that is stored on the processor if your just changing to a new IP address.


    · Save project


    · Open Controller tab
    · Select Write All


    · Select Write


    · Make sure you get the Write to M1 960-20 Complete in the Message Central window


    · Select Communications
    · Enter New IP address info


    · Open Controller tab
    · Select Transfer to Flash/EEPROM…


    · Select Transfer


    · Select Yes to stop the controller

    · Make sure you get the Write to M1 960-20 Complete in the Message Central window
    · Recycle power to your Momentum processor to make sure all changes were saved


    · When the processor powers up and the LAN LED on the processor stays on steady try to ping the new IP address

    · Open Controller tab
    · Select Start/Stop…

    · Select Start

    · Make sure you get the Controller is Running in the Message Central window
    · Check your logic and make sure all is fine