    Reconnect To The '140NOE771xx' Fails, if the Connection Is Lost To The Connexium Fiber Optic Switch.

    Goals and Symptoms


    Explain why the programming panel software (i.e.., 'ProWORX 32', 'ProWORX NxT' and Concept) fails to
    reconnect to the PLC, if the '140NOE771xx' Ethernet module's physical TCP/IP connection to Connexium
    Fiber Optic switch is lost. This is found to only happen when multiple Connexium switch are linked
    together using the Fiber Optic connection.

    Facts and Changes


    If the programming panel software (i.e., 'Concept', 'ProWORX NxT' or 'ProWORX 32') that is connected to the
    PLC via a '140NOE771xx' Ethernet module suddenly gets disconnected, the PLC could be logged back into
    without any problem, when the physical TCP/IP connections are each connected to the same Connexium switch.

    If the programming panel software (i.e., 'Concept', 'ProWORX NxT' or 'ProWORX 32') that is connected to the
    PLC through an '140NOE771xx' module suddenly gets disconnected, attempts to immediately reconnect to the
    PLC module could fail when the physical TCP/IP connections are each located on separate Connexium switches
    that are linked by a Fiber Optic cable). Further attempts to reconnect immediately after the first attempt will also
    fail.

    • Concept will return the following message.-

     
    • Message Central in 'ProWORX 32' will return the following message:.

     
    • ProWORX NxT will return the following error message.


     
    Causes and Fixes

    The problem occurs because not enough time has been allowed for the port on the Connexium
    switch to get reset.

    To resolve the problem, wait approximately 2-3 minutes before attempting a reconnection to the PLC