    May Zone Selective Interlocking and Setting Groups A and B be utilized at the same time?

    Issue
    User wishes to know if Zone Selective Interlocking (ZSI) and Setting Groups A and B may be used concurrently

    Product Line
    Sepam series 20
    Sepam series 40
    Sepam series 80

    Environment
    Setup

    Resolution
    Sepam series 20:
    Zone selective interlocking (ZSI) OR the swapping of the settings group based on an input may be used. ZSI and Setting Groups A and B may NOT be used concurrently.
    When ZSI is selected in the relay, Setting Groups A and B are replaced by the Time-based protection function and the ZSI protection function.

    Sepam series 40 / Sepam series 80
    ZSI and Setting Groups A and B may be used concurrently