    Is it possible to clear alarms and reset the SEPAM relay using the Logic Equation Editor or any other way?

    Issue
    User would like to know the options to clear alarms and/or reset SEPAM relay

    Product Line
    SEPAM series 20
    SEPAM series 40
    SEPAM series 60
    SEPAM series 80

    Resolution

    SEPAM Series 20
    The SEPAM Series 20 does not have the Logic Equation Editor, so therefore it isn't possible to create logic to clear alarms or reset the SEPAM Series 20. The only way of performing these functions in the Series 20 relay is using the Advanced UMI, SFT2841, or by sending commands via communications using PME or a third-party supervisory software.

    SEPAM Series 40
    The SEPAM Series 40 does have the Logic Equation Editor, but the user is unable to create logic to clear alarms or reset the SEPAM relay. The only output variables from "Circuit breaker control" that are available to the user are V_TRIPCB, V_CLOSECB and V_INHIBCLOSE. The only way the SEPAM Series 40 can clear alarms or reset the SEPAM relay is by using the Advanced UMI, SFT2841, or by sending a reset command via communications using PME or a third-party supervisory software.



    SEPAM Series 60
    The SEPAM Series 60 does have the Logic Equation Editor and the user is able to create logic to clear alarms or reset the SEPAM relay. When using the "Editor Assistance", the user will be able to use two separate logic functions "V_Clear" & "V_Reset" which can be programmed to perform these desired tasks. These functions can be very useful when the user is experiencing nuisance alarms and would like to frequently clear them and reset the relay. These functions can also be performed using the Advanced UMI, SFT2841, or by sending a reset command via communications using PME or a third-party supervisory software.




    SEPAM Series 80
    The SEPAM Series 80 does have the Logic Equation Editor and the user is able to create logic to clear alarms or reset the SEPAM relay. When using the "Editor Assistance", the user will be able to use two separate logic functions "V_Clear" & "V_Reset" which can be programmed to perform these desired tasks. These functions can be very useful when the user is experiencing nuisance alarms and would like to frequently clear them and reset the relay. These functions can also be performed using the Advanced UMI, SFT2841, or by sending a reset command via communications using PME or a third-party supervisory software.

    Another way to clear alarms or reset the SEPAM series 80 relay is by use the Logipam function if this option is available in the Cartridge