    How does the InH fault inhibit assignment work on the ATV61 and ATV71 drives?

    Issue:
    How does the InH fault inhibit assignment work on the ATV61 and ATV71 drives?

    Product Line:
    Alitivar ATV61 and ATV71

    Environment:
    All

    Cause:
    Needs to have an input that disables all faults for an firemans override.

    Resolution:
    1.8 Menu Fault inhibition hold the enter button down for 2 seconds to program.
    The logic input that s assigned to InH input when turned on will make fault the monitoring inactive.
    When the input goes back to 0 or off the fault monitoring is active again.

    Caution:
    -Inhibiting faults results in the drive not be protected.  This voids warranty on the   drive.
    -Check that the possible consequences do not present any risk.
    -Failure to follow these instructions can result in equipment damage.