    What is the CFF fault on the ATS48 soft starter and what causes it?

    Issue:
    What is the CFF fault on the ATS48 soft starter and what causes it?

    Product Line:
    Altistart 48, ATS48

    Environment:
    All models, all serial numbers.

    Cause:
    Invalid configuration on power up.  This could be due to a replaced control board or electrical interference that prevents the control board from reading the configuration.

    Resolution:
    This fault is due to an Internal configuration error.
    Complete a Factory Reset by going to drC menu > FCS parameter> change to YES.  Hold Enter button for 2s to complete this reset.  Reprogram the softstart.
    Cycle power to the softstart.  Then provide a new run command.
    If the fault persists after these steps, replace the control board or Softstart as applicable.