    Why would a NW frame breaker read half the expected current?

    Issue:
    During secondary injection the breaker is only indicating half of the injected current.

    Product Line:
    NW Frame Breakers

    Environment:
    FFTK testing a NW breaker.

    Resolution:
    This will happen when a W frame (standard width) breaker is being tested as a Y frame (double-wide) breaker.  The FFTK defaults to testing as a Y frame.  
    To get a good test, on the setup screen where you select breaker type, choose NW40b or test as an IEC breaker.  This will force it to recognize it as a W frame and test it correctly.