    What can cause the secondary control power transformer fuse to blow on an enclosed drive?

    Issue:
    The secondary fuse of the control transformer is blowing.

    Product Line:
    S-Flex 21, S-Flex 212, E-Flex, M-Flex

    Environment:
    All models and serial numbers

    Cause:
    Caused by short circuit to ground.  Possible loose wire or defective or damaged contactor coil.

    Resolution:
    Trace short circuit with ohm meter.  Replace coil if necessary.