    What is a bPF fault on the ATS22 soft starter?

    Issue:
    What is a bPF fault on the ATS22 soft starter?

    Product Line:
    Altistart ATS22

    Environment:
    All

    Cause:
    Bypass contactor detected fault

    Resolution:
    Check for a welded bypass contactor or shorted SCR
    If you find a shorted SCR or bypass contactor you will need to replace the soft starter.
    Reference manual BBV51330 ATS22 installation guide.