    How do I set up basic programming on an ATV61/71 drive?

    Issue:
    How do I set up basic programming on an ATV61/71 drive?

    Product Line:
    Altivar 61, Altivar 71

    Environment:
    All

    Cause:
    Basic programming to operate an ATV61 or ATV71 drive

    Resolution:

    Menu 1.1 Simply start
    tCC= 2/3 wire control (set to 2 wire control for most installations)
    bFr= Standard motor frequency - typically 60hz
    nPr= Rated motor power= HP size of the motor
    UnS= Rated motor voltage =  motor voltage
    nCr= Rated motor current= motor amps
    FrS= Rated motor Frequency= typically 60hz
    NSP= Rated motor speed= motor speed in rpm
    fFr= Max Frequency= Hz
    ItH= Motor Thermal Current= Amps (provides overload protection to the motor)
    ACC= Ramp up time acceleration
    DEC= Ramp down time deceleration
    LSP= Low speed setting
    HSP=High speed setting

    Menu 1.3 Settings Menu.
    CLi= Motor current limit (Typically set to 120% (ATV61) or 150% (ATV71) of the motor nameplate full load amps, FLA.)

    Menu 1.6 Command Menu
    Ref.1 channel= AI1 for 0-10VDC control (possibly from a potentiometer)
                          = AI2 for analog input 4-20mA control
                          = HMI for Graphic display terminal (keypad)
                          = (See the ATV61 programming manual for other options)
    Profile= Not separate- Reference and command, not separate
              = Separate- Separate reference and command
              = I/O Profile
    Ref. 2 switching= [ch1 active] (Fr1): No switching, [Ref.1 channel] (Fr1) active
                             = [ch2 active] (Fr2): No switching, [Ref.2 channel] (Fr2) active
                             = [LI1] (LI1)
                             = (See the ATV61 programming manual for other options)

    ATV61 Quick Start manual is available for download here:  https://www.schneider-electric.us/en/download/document/S1B86974/
    ATV61 Programming Manual is availalbe for download here: https://www.schneider-electric.us/en/download/document/1760649/

    ATV71 Quick Start Guide is available for download here:  https://www.schneider-electric.us/en/download/document/S1B86982/
    ATV71 Programming Manual is available for download here: https://www.schneider-electric.us/en/download/document/1755855/