    How can I monitor the logic inputs status in Ethernet TCP/IP for ATV61 and ATV71 ?

    Issue:
    How to monitor the logic input map to determine status of the logic inputs.

    Product Line:
    Altivar 61/71

    Environment:
    All Models and serial numbers.  Ethernet IP with Assemblies 100 and 101 with Profile as I/O

    Cause:
    None

    Resolution:
    To monitor the state of the logic inputs add logic address 5202 in the input scanner.  This is a read only and allows monitoring of the logic input map.  The map is as follows.
    Bit 0 is LI1
    Bit 1 is LI2
    Bit 2 is LI3
    Bit 3 is LI4
    Bit 4 is LI5
    Bit 5 is LI6
     