    ATV71: Why is the drive tripping on an INF8 code, (internal power supply fault)?

    Issue:
    ATV71: Why is the drive tripping on an INF8 code, (internal power supply fault)?

    Product Line: 
    Altivar ATV61 and ATV71

    Environment:
    All types

    Cause:
    The control supply voltage is to incorrect.

    Resolution:
    Check the control supply voltages between +24vdc and com or +24V and 0V. 
    If using an external supply check +24Vdc supply connect between P24 and 0V, and insure the voltage is greater than 19Vdc and does not exceed 30vdc.