    ATV71: Why is the drive tripping on an INF8 code, (internal power supply fault)?

    Issue:
    ATV71 is tripping on an INF8 fault.
    Product Line: 
    Altivar ATV61 and ATV71
    Environment:
    All types
    Cause:
    The control supply voltage is to incorrect.
    Resolution:
    Check the control supply voltages on +24vdc and com or +24V and 0V. 
    If using an external supply +24Vdc supply connect to P24 to 0V, and insure the voltage is greater than 19Vdc and does not exceed 30vdc.