    Video: How do you wire the ATS22 with S6U suffix for 2 wire control?

    Issue:
    Wiring the ATS22 with S6U suffix for 2 wire control

    Product Line:
    Altistart 22, ATS22

    Environment:
    All of the Altistart 22, ATS22 ending with S6U suffix (120V)

    Cause:
    Basic wiring examples

    Resolution:



    The S6U requires constant 120VAC to terminals CL1 (hot) and CL2 (neutral). 

    Connect a jumper from Terminal LI1 to LI2.  
    Connect a jumper from Terminal CL2 to COM.
    Close a dry contact between Terminals CL1 and LI2 for a run forward.  Open this connection for a freewheel stop. 

    For a controlled stop, do not jumper LI1 to LI2, jumper LI1 to CL1, use run contact between CL1 and LI2, and program SEt - dEC = ramp down time.

    Reference the User manual # BBV51330 or the Quick Start Annex # S1A14738 for more information.