    Video: What causes an INF6 fault on the ATV61 and ATV71 drives?

    Issue: 
    Troubleshooting INF6 Fault on Altivar 61 & 71 Drives

    Product Line:
    Altivar ATV61 and ATV71

    Environment:
    All products

    Cause:
    The control terminal card may be loose or there may be 2 serial communication cards installed at once.

    Resolution: 
    INF6 is an internal option fault.  Basically, the option card installed on the VFD is not recognized.
    First, re-seat the control terminal card.  Then, check the 1.11 Identification menu for option 1 and option 2 to see if there are 2 conflicting option cards installed.