    Why will the analog output not change when the AO1 assignment is set to Torque 4Q?

    Issue:
     The Analog output is fixed at 50% and not changing as the torque in the motor changes (Fixed at 10mA when the Analog output is set to 0-20mA, fixed at 12 mA when the Analog output is set to 4-20mA)
     
    Product Line:
     Altivar 71
     
    Environment:
     All part numbers all versions
     
    Cause:
     The motor control type is set to either V/F 2pts or V/F 5pts
     
    Resolution:
    The Motor control type must be set to something other than V/F 2pts or V/F 5pts for this function to work.   Once the Motor Control type has been changed the analog output should begin to respond to changes in the motor torque.