    What is the cause of the EF2 fault code on the ATV21 and ATV212 drives?

    Issue:
    ATV212: EF2 Fault

    Product line:
    Altivar ATV212

    Environment:
    All models, all serial numbers

    Cause:
    Ground Fault on the output of the drive.

    Resolution:
    EF2= Ground Fault

    Troubleshooting tips
    • Check the motor ground connections. Make sure the ground is going to the chassis of the drive.
    • Remove the motor leads from the drive and Megger with a 1KV Megger to see if there is a short to ground in the motor windings.

    Reference the ATV212 programming manual S1A53838 (attached).