    How to set up an ATV12 drive so that R1 relay closes upon motor run status?

    Issue:
    How to set up an ATV12 drive so that R1 relay closes upon motor run status?

    Product line:
    Altivar 12, ATV12
     
    Environment:
    All models, all serial numbers
     
    Resolution:
    The Altivar 12 has an NO/NC programmable contact on terminals R1A-R1B-R1C.  (NO is R1A to R1C, NC is R1B to R1C). 
    Relays accept both a 120V source or 24VDC.

    To setup R1 to indicate the drive is running you need to assign this function to the R1 relay.
    Go to the following menu:
    COnF > FULL > I_O- > r1.  Change this parameter to rUn
    When the drive is providing voltage to the motor, the R1A-R1C contact will be closed. 
    See User Manual BBV28581 for more details.