    ATV61/71: How is a 2 wire, 4-20mA transducer wired to the drive?

    Issue:  
    How is a 2 wire, 4-20mA transducer wired to the drive?

    Product line:
    Altivar ATV61 and ATV71

    Environment:
    All models, all serial numbers 

    Cause: 
    A 2 wire transducer needs to be wired to the drive for a pressure feedback signal.  
     
    Resolution:
    Wire the 2 wire transducer as follows:
    The input of the transducer typically requires 24Vdc.  This may be wired to the VFD terminal +24 or to an external power supply.
    The output of the transducer is wired to the VFD terminal AI2.
    Program the AI2 Configuration for 4-20mA.  See attached file.