    Altivar 61/71 what is the recommended corrective action when the motor runs in reverse with a run forward command?

    Issue:
    The motor is running backwards with a forward run command on the drive.

    Product line:
    Altivar ATV61 and ATV71

    Environment:
    All models, all serial numbers

    Cause:
    The phase rotation is inverted coming out of the drive going to the motor.
        
    Resolution:

    Option 1:
    To correct the motor rotation swap two motor leads on the drive output terminals.

    Option 2:
    Go in the simple start menu 1.1 find output phase rotation change it from ABC to ACB.
    Refer to the ATV61 and ATV71 programming manuals.