    How is the ATV212 set for HMI controls for both RUN/STOP and speed reference?

    Issue:
    How is the ATV212 set for HMI controls for both RUN/STOP and speed reference?

    Product Line:
    Altivar 212

    Environment:
    All models

    Cause:
    Control for VFD to be from the HMI

    Resolution:
    There are several options.
    1) Put the VFD in Local Mode by pressing the LOC/REM button on the integral keypad, or the F4 button on the remote keypad.  Indicators for Local Mode are the green LED is ON for LOC/REM, or LOC is displayed above the F1 button.
    2) Keep the VFD in Remote Mode and set CMOd=1 and FMOd=3

    Both of these options apply for integral keypad or remote keypad control.