    What causes a bOF fault code on ATV61 and ATV71 drives?

    Issue:
    What causes a bOF fault code on ATV61 and ATV71 drives?

    Product Line:
    ATV61, ATV71

    Environment:
    All serial numbers, all model numbers.

    Cause:
    Drive showing 'bOF' on the display.

    Resolution:
    If the DB resistor protection is set to Freewheel (yes), the drive faults on bOF on power up.  This is because the drive is looking for a DB resistor connected.  
    Set parameter brP (DB resistor Protection) to NO or check the resistor that is connected to the PA and PB connections.

    CTA-ID : 2062030