    Video: How can you program the ATV212 drive to follow 0-10vdc speed signal on VIA and start/stop via terminal control?

    Issue:
    How can you program the ATV212 drive to follow 0-10vdc speed signal on VIA and start/stop via terminal control?

    Product Line:
    Altivar ATV21 and ATV212

    Environment:
    All

    Cause:
    Wants to use VIA for 0-10vdc speed control and start stop via 2 wire control thru the terminal inputs.

    Resolution:
    Switch VIA SW100 setting:  Set the switch on the main circuit board to U for an 0-10vdc input signal on VIA.
    Wiring= 0-10vdc signal to VIA and CC    two wire start dry contact is wired between P24 and F.
    Programming set FNOD= 1 VIA CNOD= 0 terminal control,  F111= 2  for 2 wire control.
    Basic programming
    uLu= motor voltage
    F415= normal motor current
    F417= normal motor RPMs