    What is the fault code PRA on ATV61 or ATV71 drives?

    Issue:
    What is the fault code PRA on ATV61 or ATV71 drives? 

    Product Line:
    Altivar ATV61 ATV71

    Environment:
    All

    Cause:
    Drive status is showing PRA on the HMI display.

    Resolution:
    PRA is not a fault, but it is a drive state, meaning that the power removal function is active. The drive is not detecting 24Vdc on the PWR terminal.
    Measure for 24Vdc between +24 - COM to verify the internal power supply.
    Confirm that the factory installed jumper between +24 and PWR is solidly connected.  The jumper is removed if a safety circuit is installed.  Verify continuity of the safety circuit.

    When the voltage on PWR is re-established, the drive status will return to RDY if there is not an active run command, or NST if a run command is active.  To clear NST, remove the run command.
     