    When programming the ATS48 analog output for motor current scaled?

    Issue:
    When programming the ATS48 analog output for motor current, AO=OCr, is the scaling parameter ASC a percentage based on the motor current parameter In or based on the nameplate current rating of the specific ATS48?
     
    Product Line:
    Altistart 48, ATS48
     
     Environment:
     All
     
    Cause:
    Programming the ATS48 analog output for motor current.
     
    Resolution:
    It is based on the motor current programmed into In.  It is adjustable from 50 to 500% of the In value.

     