    Can you interconnect A-Links CW and DX InRow Cooling products?

    Issue:
    Can you interconnect A-Links CW and DX InRow Cooling products?
    Product line:
    ACSC, ACRD, ACRC
    Environment:
    DataCenter InRow Cooling
    Cause:
    Resolution:
    The key to grouping is if the units share the same firmware then they can be grouped.  So the ACRP10x, ACRP50x, ACRD50x and ACRC50x can all be grouped with "like" units (CW to CW, DX to DX). The ACRD10x and ACRD20x can be grouped together, but not with the others. The ACRC10x can only be grouped with itself and the same goes for the ACSC10x. The Gen2 units can not be grouped with the Gen1 units. The ACRD60x and ACRC60x can not be grouped with the ACRP10x or the ACRC50x units. Same with the ACRC301 CW units can not be grouped with the ACRC10x units.

    Examples:

    1) Cannot A-Link / Group
    A) ACRD1xx + ACRP1xx +ACRD5xx on the same A-Link
     
    B) ACRC1xx +ACRC5xx on the same A-Link

    2) Can A-Link / Group
    A) ACRP1xx + ACRD5xx on the same A-Link
     
    B) ACRP5xx + ACRC5xx on the same A-Link
     


    Just to clarify, it's "like" units, so 600mm DX with other 600mm DX; and 600mm CW with other 600mm CW; however, 600mm CW and 600mm DX can NOT be grouped, even though they share the same FW.

    Here is a general list (all within the same category can be grouped).
    600mm DX
    ACRP100
    ACRP101
    ACRP102
    ACRD500
    ACRD501
    ACRD502

    600mm DX Gen2
    ACRD600
    ACRD601
    ACRD600P
    ACRD601P

    600mm CW
    ACRP500
    ACRP501
    ACRP502
    ACRC500
    ACRC501
    ACRC502

    600mm CW Gen2
    ACRC600
    ACRC601
    ACRC600P
    ACRC601P

    300mm 10kW DX
    ACRD100
    ACRD101
    ACRD200
    ACRD201

    300mm CW
    ACRC100
    ACRC103

    300mm CW Gen2
    ACRC301S
    ACRC301H

    300mm 5kW DX
    ACSC100
    ACSC101

    Pumped Refrigerant Cooling System (PRCS, R134a...)
    ACDA901
    ACOA500
    ACOA501
    ACRA100
    ACRA101


    For 300mm Units and Pumped Refrigerant:
    Install the terminator on the left-hand side A-link ports on the first unit. The left-hand side is the in port. The right-hand side is the out port


    For 600mm Units:
    Follow the labels on the A-Link ports. The top port is the in port and the bottom port is the out port.