    Symmetra PX 250/500: What happens when EPO is activated?

    Issue:
    Symmetra PX 250/500; What does the EPO (Emergency Power Off) trip
     
    Product line:
    Symmetra PX 250/500
     
    Environment:
    All serial numbers
     
    Cause:
    What occurs when the EPO on a Symmetra PX 250/500 button is engaged?
     
    Resolution:
    When the EPO is activated, UPS output breaker Q2 and the battery breakers are tripped. The Power Modules (inverter) and if in Static Bypass operation will the UPS turn off