    Why does a Smart-UPS turn off when a standard serial cable is attached?

    Issue:
    Why does a Smart-UPS turn off when a  standard serial cable is attached?

    Product Line:
    Smart-UPS

    Environment:
    All SU, SUA, SURT, and SUM  models, All Serial Numbers

    Cause:
    A Smart-UPS may turn off if a standard serial cable is connected. This is due to the proprietary pinout of APC Smart-UPS serial cables.

    Resolution:
    Always make sure a proper APC Serial Cable such as the 940-0024, 940-1524, or 940-0020 is being used. APC Serial Cables will always have part number clearly marked on the connector end of the cable. 
    SMT, SMX, SMC, and SRT models use a new Keyed RJ45 to DB9 cable to further differentiate between the APC cable and a standard serial cable.
     