    Can you use a GFI (Ground fault interrupt) on a 115V single phase input with a ATV11 drive?

    Issue:   Can you use a GFI (Ground fault interrupt) on a 115V single phase input with a ATV11 drive?
     
    Product Line:   ATV11
     
    Environment:  All
     
    Cause:   Feeding the ATV11 with GFI
     
    Resolution:   
    The PWM in the drive can cause problems with the GFI, because of the capacitance to ground. It is not recommend to use a GFI with the drive.
    If a GFI have to be used, then suggest installing an isolation transformer between the GFI and the drive. Also the motor needs to be properly grounded.


     