    What are the UL and IEC ratings for the Merlin Gerin C60 breakers?

    Issue:  
    What standards do Multi 9 C60 breakers conform to? 

    Product Line:
    Multi 9 C60 Breakers 

    Environment:  
    Multi 9 UL and IEC C60 type breakers

    Resolution:
    Ratings per UL Standards     UL 489/CSA C22.2 No.5 C60   UL 489/CSA C22.2 No.5 C60  
          (240 Vac)       (480Y/277 Vac)    
    Number of Poles     1P 1P 2P 3P 1P 2P 3P  
    Rated Current at 77°F (25°C)     0.5–20 A 25–35 A 0.5–35 A 0.5–35 A 0.5–20 A 1–20 A 1–20 A  
        120 V 10 kA 10 kA 10 kA  
      AC 50/60 Hz 240 V 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA  
    Interrupting Ratings   277 V 10 kA 10 kA 10 kA  
    as per UL 489/CSA C22.2 No.5   480Y/277 V 10 kA 10 kA  
      DC 60 V 10 kA 10 kA 10 kA  
        125 V 10 kA  
                         
    Ultimate Breaking Capacity (Icu) AC 50/60 Hz 240 V 10 kA 10 kA 20 kA 20 kA 10 kA 10 kA 10 kA  
    as per IEC 60947-2 Standard   415V 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA  
        440V 6 kA 6 kA 6 kA 6 kA  
    Ratings per UL Standards      UL 1077 C60            
    Number of Poles     1P 2P 3P 4P        
    Rated Current at 77°F (25°C)      0.5–63 A  0.5–63 A  0.5–63 A  0.5–63 A        
        120 Vac 10 kA        
      50/60 Hz 240 Vac 10 kA 10 kA 10 kA 10 kA        
    Interrupting Ratings   277 Vac          
    as per UL 1077   480Y/277 Vac              
        65 Vdc 10 kA        
        125 Vdc 10 kA        
        240 V 10 kA 20 kA 20 kA 20 kA        
    Ultimate Breaking Capacity (Icu) AC 50/60 Hz 415V   10 kA 10 kA 10 kA        
    as per IEC 60947-2 Standard   440V 6 kA 6 kA 6 kA        
                         
    Ratings per IEC 60947-2    N40  C60N  C60H  C60L  C120H
    Number of Poles   1 (Ø + N) 1 2, 3, 4 1 2, 3, 4 1 2, 3, 4 1 2, 3, 4
    Rated Current 25°C (77°F) In 1–40 A  1–63 A 1–63 A 1–40 A  1–40 A 1–25 A 1–25 A
    Rated Current (A) 40°C (104°F) In  —  —  —  —  —  —  — 63–125  63–125
    Rated Voltage Ue 230 V 440 V 440 V 440 V 440 V 440 V 440 V 440 V 440 V
      130 Vac  —  —  —    —  —  —    —
      230–240 Vac 7.5 kA 10 kA 20 kA 15 kA 30 kA 25 kA 50 kA 15 kA 30 kA
      400–415 Vac 2 kA 3 kA 10 kA 4 kA 15 kA 6 kA 25 kA 4 kA 15 kA
    Ultimate Breaking Capacity (Icu) 440 Vac  —  — 6 kA  — 10 kA  — 20 kA  — 10 kA
    as per IEC 60947-2 Standard 1P 60 Vdc  — 15 kA  — 20 kA  — 25 kA  —  —  —
      2P 125 Vdc  —  — 2P 20 kA  — 2P 25 kA  — 2P 30 kA  —  —
         —  — 3P 30 kA  — 3P 40 kA  — 3P 50 kA  —  —
      3P 250 Vdc  —  — 4P 40 kA  — 4P 50 kA  — 4P 60 kA  —  —