    How can input phase loss fault be disabled with the Altivar 58 drive?

    Issue:
    How can input phase loss fault be disabled with the Altivar 58 drive?

    Product Line:
    Altivar 58

    Environment:
    All

    Cause:
    N/A

    Resolution:
    Go to menu 6 (FLt - fault menu)
    Set the IPL  parameter (Input Phase Loss) to no.
    This will allow the drive to continue running without PHF fault if there is a loss of input phase voltage. This does not disable other faults in the drive.
    See keypad programming manual for additional details.