    What is the part number for the replacement 5.0P trip unit for NW Masterpact molded case breaker like NW30H?

    Issue:
    What is the part number for the replacement 5.0P trip unit for NW Masterpact molded case breaker like NW30H?

    Product Line:
    NW Masterpact

    Cause:
    Need to replace trip on a NW Masterpact

    Resolution:
    S163A is the replacement field installable Micrologic Trip Unit.

    Other trip unit options include
    Model Protection Cat. #
    2.0 (IEC only) LSO S132R
    3.0 (UL/ANSI only)  LI S131A
    5.0 LSI S133A
    2.0A (IEC only) LSO S142R 
    3.0A (UL/ANSI only)  LI S141A 
    5.0A LSI S143A 
    6.0A LSIG S144A 
    5.0P LSI S163A
    6.0P LSIG S164A
    5.0H LSI S173A
    6.0H LSIG S174A


    See instruction bulletin, Powerpact P, R, and Masterpact NW, NT Micrologic™ 5.0P and 6.0P Trip Units, see 48049-137-05

    Didn’t find what you were looking for?

    Try Searching Again View Our Categories

    Need further assistance?

    Our Customer Care department provides total customer service solutions for our residential, industrial and commercial applications.

    Get Assistance